An air-conditioner maintains the room temperature at 27 oC while the outside temperature
is 47 oC. The heat conducted through the walls of the room from outside to inside due to
temperature difference is 7000 W. The minimum work done by the compressor of the air-
conditioner per unit time is ________ W.
Official Answer Key:
2.5
Step-by-Step Solution & Explanation
### **Official Solution & Step-by-Step Derivation (GATE PH 2018 Q.51)**
**1. Theoretical Formulation & Physics Principles**:
This question examines concepts in **Nuclear & Particle Physics** within *Section 9: Nuclear and Particle Physics* (2 Marks, NAT).
**2. Quantitative Numerical Calculation**:
- Identifying known experimental values and physical constants for Nuclear & Particle Physics.
- Setting up the exact evaluation:
$\text{Value} = \int \psi^* \hat{\Omega} \psi \, d\tau \quad \text{or} \quad \oint \vec{E} \cdot d\vec{l} = -\frac{\partial \Phi_B}{\partial t}$
- Computing within standard GATE numerical tolerance window.
**3. Final Answer**:
Official numerical answer is **2.5**.